Data Cable Separation Distance from Source of Interference


Unshielded data cables should not be installed near sources of electromagnetism.

IA/TIA-569, the cabling pathways standard for data cables, specifies these minimum separation distances for structured data cabling systems with a power source of 480V or less.

Location Condition < 2 kVA 2-5 kVA > 5 kVA
Unshielded power lines or electrical equipment in proximity to open or non-metal pathways 5 in 12 in 24 in
Unshielded power lines or electrical equipment in proximity to grounded metal conduit pathway 2.5 in 6 in 12 in
Power lines enclosed in a grounded metal conduit or equivalent shielding (in proximity to a grounded metal conduit pathway) --- 6 in 12 in
Transformers and electric motors 40 in 40 in 40 in
Fluorescent lighting 12 in 12 in 12 in