Data Cable Separation Distance from Source of Interference
Unshielded data cables should not be installed near sources of electromagnetism.
IA/TIA-569, the cabling pathways standard for data cables, specifies these minimum separation distances for structured data cabling systems
with a power source of 480V or less.
Location Condition |
< 2 kVA |
2-5 kVA |
> 5 kVA |
Unshielded power lines or electrical equipment in proximity to open or non-metal pathways |
5 in |
12 in |
24 in |
Unshielded power lines or electrical equipment in proximity to grounded metal conduit pathway |
2.5 in |
6 in |
12 in |
Power lines enclosed in a grounded metal conduit or equivalent shielding (in proximity to a grounded metal conduit pathway) |
--- |
6 in |
12 in |
Transformers and electric motors |
40 in |
40 in |
40 in |
Fluorescent lighting |
12 in |
12 in |
12 in |